Remote Monitoring
LED Indicator
HMI Interface for remote Parameter Setting&Alarm Mute
IEC60364-7-710:2016; IEC 61557-8-2007; EMC
Remote Monitoring (Duplicate data of AIM Series Insulation monitor) ● Insulation Fault ● Alarm ● Operating Message ● Through RS485 (MODBUS-RTU) |
|
LED Indicator ● On-off status of devices ● Insulation Fault ● Overload ● Over-temperature |
|
HMI Interface for remote Parameter Setting&Alarm Mute ● Set Response Time of Insulation Monitoring ● Mute Audible Alarm | ![]() |
Parameters/Model | AID10 | AID120 | AID150 | |
| Auxiliary power | Voltage | DC 24V | ||
| Power consumption | < 0.6W | |||
| Insulation resistance measurement range | — | 0—999kΩ | — | |
| Insulation alarm value range | 50—999kΩ | |||
| Transformer load rate display | — | Percentage display | — | |
| Load current alarm settings | 14A、18A、22A、28A、35A、45A | |||
| Temperature alarm value range | 0~+200℃ | |||
| Alarm | Audible and visible alarm | |||
| Alarm Type | Insulation fault, overload, over-temperature, equipment failure | |||
| Communication | RS485 interface, MODBUS-RTU protocol | |||
| Display method | — | LED Display | 128*32 LCD | |