● Measurement: 3-phase kWh (0.5S), Active Power, Reactive Power, Current, Voltage, Harmonic and etc
● Voltage Rating: 3x220/380V, 3x57.7/100V (3P4W); 3x380V, 3x100V (3P3W)
● Current Rating: 3x10(80)A; 3x1(6)A
● Frequency: 45~65Hz
● Commnunication: RS485 (MODBUS-RTU) and Infrared
● Multi-rate: Spike, Peak, Valley and Flat kWh
● Extra Function: Cable Temperature Measurement and DO/DI
● Display: LCD (8 digits)
● Dimension: 127*88*70mm (L*W*H)
● Wiring: 3-phase 4wire; 3-phase 3-wire
● Installation: 35mm DIN Rail
● Standard&Certificate: IEC; CE; EAC
Acrel ADL3000/DTSD1352 is a smart meter designed for power supply systems, industrial and mining enterprises, and utilities to calculate electricity consumption and manage electric demand. Acrel adl 3000 features high precision, a small size, and simple installation. (Note: The meter can match to Solis Inverter to solar power zero export, if it is used for the Solis Inverter, please remark your Solis inverter model.)
1.Function description
Function | Function description | Function provide |
Measurement of kWh | Active kWh (positive and negative) | ■ |
Reactive kWh (positive and negative) | ■ | |
A, B, C phase positive active kWh | ■ | |
Measurement of electrical parameters | U、I、P、Q、S、PF、F | ■ |
■ | ||
Measurement of | 2~31ST Voltage and current harmonic | □Note 1 |
LCD Display | 8 bits section LCD display, background light | ■ |
Key programming | 4 keys to communication and set parameters | ■ |
Pulse output | Active pulse output | ■ |
Reactive pulse output | □Note 2 | |
Clock pulse output | □Note 2 | |
Multi-tariff and functions | Active switch input | □Note 3 |
Switch output | □Note 2 | |
Adapt 4 time zones, 2 time interval lists, 14 time interval by day and 4 tariff rates | □ | |
Max demanded kWh and time happened | □ | |
Frozen data on last 48 months, last 90days | □ | |
Date, time | □ | |
Communication | Infrared communication | ■ |
The first communication path: Communication interface: RS485, Communication protocol: MODBUS-RTU | □ | |
The second communication path: Communication interface: RS485, Communication protocol: MODBUS-RTU | □Note 3 | |
Temperature measurement | Support 3 outlay NTC temperature | □Note 4 |
“■” means standard, “□” means optional.
2.Technical parameter
Specification | 3 phase 3 wires, 3 phase 4 wires | |
Voltage | Reference voltage | 3×100V、 3×380V、3×57.7/100V、 3×220/380V |
Consumption | <10VA(Single phase) | |
Impedance | >2MΩ | |
Accuracy class | Error±0.2% | |
Current | Input current | 3×1(6)A (second connection with 3- phase load line via extra selected CTs) 3×10(80)A (direct connection with 3-phase load line via CTs built in ADL3000-E) |
Consumption | <1VA(Single phase rated current) | |
Accuracy class | Error±0.2% | |
Power | Active, reactive, apparent power, error±0.5℅ | |
Frequency | 45~65Hz, Error±0.2% | |
Temperature | -40℃~99℃ | |
Energy | Active energy(Accuracy class:0.5, 1), reactive energy(Accuracy class 2) | |
Clock | ≤0.5s/d | |
Energy pulse output | 1 active optocoupler output, 1 reactive optocoupler output | |
Switching output | 1 Switching output | |
Switching input | 1 optocoupler input | |
Width of pulse | 80±20ms | |
Pulse constant | 6400imp/kWh,400imp/kWh(Correspond with the basic current) | |
Interface and communication | RS485:Modbus RTU | |
Range of communication address | Modbus RTU:1~ 247; | |
Baud rate | 1200bps~19200bps | |
Relative temperature | -25℃~+55℃ | |
Relative humidity | ≤95℅(No condensation) |
Diverse Electricity Parameters Measurement ● Harmonic (2~31st voltage¤t)---Optional ● F (Frequency) ● U (3-phase Voltage) ● I (3-phase Current) ● kWh (3-phase positive Kilowatt-hours) ● kVarh (Kilovar-hours) ● P (Power) ● Q (Reactive power) ● S (Apparent power) ● PF (Power factor) | |
Multi-rate/Flexible Tariff ● 4 Time zone ● 4 Tariff rate (Spike, Peak, Flat, Valley) ● 2 Time period list ● 14 Time period by day ● Data Frozen (last 48 months or last 90 days) ● Max demand and occurrence time | |
2 Channel RS485 Communication ● Protocol: MODBUS-RTU ● 1 channel RS485 or 2 channel RS485 both optional | |
3-channel Temperature Measuring ● Thermistor: NTC temperature sensor ● Measuring Range: -40℃~+125℃ | |
DO/DI Switch ● 1 channel DO ● 1 channel DI | |
HMI for Parameters Setting ● Code ● Protocol ● Address ● Baud rate ● Parity ● All Display | |
Infrared Communication for Remote Meter Reading ● Built-in infrared communication ● Easy Remote Meter Reading ● Optional Connection Methods ● Direct Connection with Meter ● First Connection via CT. | |
Optional Connection Methods ● Direct Connection with Meter ● First Connection via CT. |